There is no row at position 0.There is no row at position 0. CEGCO


STATISTICS IN (2021)

Power Station Generated energy Consumed energy Sent out energy Fuel Consumption
  (MWh) (MWh) (MWh) (GJ)
ATPS 140,559 23,288 129,746 1,518,223
Rehab 220,689 6,901 214,022 2,243,138
Risha 466,475 1,491 461,402 6,427,582
Total CEGCO 827,723 31,680 805,170 10,188,943


PERFORMANCE INDICATORS IN (2021 )

Power Station Availability Unplanned outage Factor  Planned outage Factor  Efficiency (%) Heat rate (KJ/kWh)
  ( % ) ( % ) ( % ) Sent out Sent out
ATPS 99.89 0.11 0.00 27.81 12,946
Rehab 99.92 0.08 0.00 34.31 10,492
Risha 98.69 0.14 1.17 26.04 13,823
Total CEGCO 99.80 0.10 0.10 28.13 12,798